Direct temperature controller is designed for setting temperature at the exit of fluid heat exchangers. Temperature controller works on the principle of direct action of the vapor pressure inside thermo
bulb (mounted in the heat transfer environment ) on an actuator which closes (open) valve through which circulating the heating (heat).
|
Limits of adjustment: |
40 ... 250 oC |
|
Adjustment range: |
30 oC |
|
Proportional Zone: max. |
12 oC |
|
Flow coefficient [kvs] |
according tab. 2 |
|
Differential pressure on valve P: |
according fig. 2 |
|
The nominal diameter of the body: |
1"; 2" |
|
Valve type: |
Quick |
|
The minimum length of the thermo bulb dip: |
340 mm |
|
The length of the capillary link: |
2; 4; 6; 8 m |
|
Working Environment (heating): |
water,steam,gas |
|
Maximum pressure fluid valve: |
16 bar |
|
Maximum pressure working environment: |
25 bar |
|
Maximum temperature working environment: |
250 oC |
|
Thermobulb material: |
CuZn sau 10TiNiCr180 |
|
Ambiental temperature |
-30 … +40 oC |